I am currently working on a project with a VRF system. We have contacted the manufacturer for non-default refrigerant leakage rate values. The value obtained of 3.13grams/year would mean almost 0% leakage rate per year.
Should I use the manufaturer's value for the calculation or is 0.5% the minimum value allowed? This make a considerable difference in the calculation.
Thanks in advance.
Dave Hubka
Practice Leader - SustainabilityEUA
LEEDuser Expert
530 thumbs up
August 22, 2016 - 3:05 pm
I would anticipate the LEED reviewer will require you to use the minimum value allowed.