NC-v4 EAp2:Minimum energy performance

90.1-2007 G3.1.1 exception d vs 90.1-2010 exception c

Exception c requires that lab spaces use a system 5 or 7 in the same way that exception d does, but exception c does not prescribe any specific turn down during unoccupied periods. Does this mean i can force the baseline to be constant volume at the design air change rate assuming my air change rate is higher than the required airflow to handle the load?

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Wed, 06/01/2016 - 14:06

No. That particular requirement was moved to the exception under G3.1.3.13 for lab spaces.