NC-2009 IEQc1:Outdoor Air Delivery Monitoring

Location of OA monitor at PAU or AHUs

Hi, my project has PAU distributes 100% OA to AHUs so I want to ask if installing 1 OA meter at PAU is sufficient for the credit or I have to install meters at every AHU? Thank you for your advice

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Tue, 10/13/2015 - 17:55

It depends on whether or not the PAU is constant volume. If it is, then one AFS or CSR for that fan is allowable. If it is variable volume, then not only is it required for LEED, but it is good for building control.