NC-v4 EQp1:Minimum indoor air quality performance

How to calculate Floor Area to be Ventilated?

Dear, I have one more question, please. In ASHRAE 62.1-2010 section 6.4.1 there is an explantion about floor area to be ventilated. I didn't understand how calculate the area if there is only the number of distance. For example, to Single Side Opening the floor area to be ventilated would be 2H*(opening width)? Thanks,

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Thu, 12/15/2016 - 21:47

This is saying that only the space within a distance of 2H from the openings can be considered to be naturally ventilated. H is the floor to ceiling height. If you have an 8 ft. ceiling, and a wall with openings, only the space within 16' of those openings can be considered ventilated from those openings. Spaces deeper than that would not comply with the natural ventilation.