I modeled a 10-story hotel building. Since the majority of space are hotel rooms, which are considered to be Residential spaces, the primary Baseline HVAC system type is System #1. Of course, there are the nonresidential spaces that exceed 20000 SF, so I modeled them with System #7. I received comments from USGBC reviewer to change the system type for IT rooms & corridors & other spaces to System #3 per G3.1.1 Exceptions b & c. My question is, since the primary HVAC system is System #1, and I'm already applying G3.1.1 Exception a to use System #7, do I have to apply Exceptions b & c on top of System #7? Thanks.