Forum discussion

Do I model part-load curve for the DES default efficiency?

The DES guideline (2010) allows us to model DES cooling plant with a COP of 4.4, which includes cooling towers and primary pumps. When we use this default efficiency, can we still apply a part-load curve? (something like 90.1 default curve) Or is it an average efficiency which already count for all part-load and full-load condition? (in which case we need to apply a flat curve to the cooling plant) Thanks.

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Mon, 02/10/2014 - 14:33

It is an average efficiency so the curve is flat.