Forum discussion

NC-2009 IEQp1:Minimum IAQ Performance

Natural Ventilation by Windows

Can an air conditioned space that has operable windows earn minimum IAQ performance prerequisite by demonstrating the compliance with natural ventilation requirements? Kindly advise.

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Tue, 09/17/2013 - 13:00

Yes, for ASHRAE 62.1-2007, it is permissable. ASHRAE 62.1-2010 however, does not permit natural ventilation of a conditioned space.

Tue, 09/17/2013 - 13:04

Yes. I have taken this approach successfully with a group of LEED certified duplex dwelling units. The air conditioning unit provides heating and cooling. The windows provide the ventilation for LEED certification purposes. We also had continuous bathroom fan ventilation to meet Energy Star ventilation requirements, but the exhaust fan was not the method used to certify for LEED.

Add new comment