Forum discussion

NC-2009 IEQc6.2:Controllability of Systems—Thermal Comfort

Multiple thermostats averaging

If one VAV box with a reheat coil is serving three private offices, would providing one thermostat for each office, and have the controls average the temperature requirement for each thermostat, and modulate the VAV/reheat coil accordingly, comply with this credits requirements?

0

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Sun, 06/09/2013 - 00:58

No, the configuration and control strategy you describe does not comply with the credit requirements. 50% of the occupants have to be able to control their environmental conditions such that each is thermally comfortable. Your scenario has the distinct possibility of having all three occupants be uncomfortable. You'd need at least 2 VAV boxes to meet the credit requirement. Hope this helps. Good luck! Best regards, John

Mon, 06/10/2013 - 17:13

This discussion may also be helpful to reference: http://www.leeduser.com/credit/NC-2009/IEQc6.2?page=0#comment-39062