We are working on a project which is mixed use facility (6 storey/G+5) . The first & 2nd floor is used for office & remaining for residential.
Please guide how to select baseline HVAC system as per ASHRAE 90.1.
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Go premium for
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5909 thumbs up
June 1, 2013 - 10:48 am
The residential is System 1 or 2. For the office see if G3.1.1 Exception a applies. If so then enter Table G3.1.1A with the office area and fuel type and select the system type. If not the whole building is system 1 or 2.