Our building is fully occupied by the same company, so all the floors have similar open space layout, except for enclosed managers or small meeting rooms. There´s an outside air intake in each AHU level. Each floor is served by one AHU, that provides a mixture of outside air with return air, on a constant volume. There are no VAV´s, no dampers and no different zones in our ventilation plenum. Since the floors are mostly open space, have no critical zones (bigger meeting rooms, in the last floor, are served by different AHUs), and are all of the same type (office space), is it wrong to consider it a single-zone system, and measure the intakes only in the AHU level? Or should I consider it a multizone and go through all the VRP calculations?
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
- A DOA, that provides outdoor air to VRF evaporators.
- Most of the evaporators in the project provides air conditioning to only one zone. These woulf be Single Zone and we should use the LEED calculator.
- - Some of them provide air conditiong to two or more zones. If I understood ok, we are dealing with a Multiple zone with recirculation. I we use the LEED calculator my questions are:
- Which would be the Er?
- In this system the Zone Discharge Airflow is the same as the Zone Primary Airflow, is this assumption right?