If the project spaces are served by a large VAV system which has mixing of central Outside air inlet and recirculation air, but the VAV system is also serving other tenant spaces. How can we do the calculation if we cannot get space use info in other tenant spaces which are served by same VAV system?
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Go premium for
Dylan Connelly
Mechanical EngineerIntegral Group
LEEDuser Expert
472 thumbs up
January 21, 2013 - 3:13 pm
This is a bit tricky, we tend to try to find the data for the other tenant spaces just to be sure. Sometimes you can get this information from the building engineer or manager.
If not, the CI version of this form allows you to only input the critical zones. "Describe how critical zones are selected and how all occupied zones are accounted for in the determination of the critical zone. A critical zone is defined as the zone which requires the largest fraction of outdoor air in the primary air stream."
If we don't have the data from all the zones, we will typically input all of the zones within the project scope then explain that the other zones are similar in the narrative (also private offices and conference rooms, etc).