Forum discussion

NC-2009 EAc1:Optimize Energy Performance

break hp vs Comercial hp

What is the correct approach when simulating pumps and fan power in the proposed case?. size the electric motors with the bhp or the next commercial motor size. I mean the if the condenser water pump has 15.3 bhp but the next available motor size is 20 hp. the pump will not use 20 hp. Thanks in advance.

2

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Tue, 05/15/2012 - 17:46

The correct approach is the one which will yield the most accurate energy use results. As you point out the bhp is more accurate.