Cooling tower's performance is covered in 90.1 Table 6.8.1G, but does its motor have to comply with Table 10.8 Minimum Efficiency for Motors?
You rely on LEEDuser. Can we rely on you?
LEEDuser is supported by our premium members, not by advertisers.
Go premium for
Marcus Sheffer
LEED Fellow7group / Energy Opportunities
LEEDuser Expert
5909 thumbs up
October 14, 2011 - 5:46 pm
The efficiency requirements in Table 10.8 are law in the US. It is not legal to make motors with lower efficiencies. So if the cooling tower motor is covered by the law it should be in compliance.
If outside the US, if the cooling tower motor is covered by the motor type in the table then yes it would need to comply.