Forum discussion

NC-2009 IEQc1:Outdoor Air Delivery Monitoring

PTHP

We are working on a hotel with PTHP units. PTHP units have manual outdoor airflow monitors that, once set, are not adjusted unless the unit is taken apart. There isn't a way to automatically monitor these units. Is this still acceptable to achieve this credit? Would it be acceptable if we provided CO2 sensors in the room instead of the automatic airflow monitors?

1

You rely on LEEDuser. Can we rely on you?

LEEDuser is supported by our premium members, not by advertisers.

Go premium for $15.95  »

Fri, 10/14/2011 - 02:42

Kristin,Can you install outdoor air monitoring devices in each space? As opposed to at the PTHP units? I do not think only installing CO2 sensors will be enough to earn this credit, since one of the requirments is to montor outdoor air flow. Anyone else have experience with this?

Thu, 04/19/2012 - 20:29

I assume that when you said "THP units have manual outdoor airflow monitors" you meant that they have manual dampers. You may be able to install an airflow monitor (which is not required to modulate the damper) in each unit. If there is no room to install one in your selected model then I think you will simply not be able to achieve this credit. Companies such as Ebtron make special application AMS's that may fit your need. Hope that helps (even if it's late).

Add new comment

To post a comment, you need to register for a LEEDuser Basic membership (free) or login to your existing profile.