Not sure I completely understand the question.
For your base case, all those numbers should be the ones in Table 7.8. For the design case, the manufacturer should provide the numbers.
Thanks Chris,
Ok as you say the base case should use the numbers in the table. Say for Electric water heaters >12kW, table says Performance required is "20+35 √V SL, Btu/h". V is the volume and SL is “stand by loss”. How can I get the SL figure?
Secondly is the “Performance Required” equal to COP?
Assuming there is no SL then the overalls result would be 20? 20 can not be a water heater COP? Normally we are talking about COP of 85% to 95% for electric water heaters.
Would you please enlighten me?
Cheers,
I think you've misinterpreted the formula.
20+35*√V=SL in BTU/H.
So for a 25 gallon tank (let's say), the maximum Standby Loss (SL) is:
20+35 *√25=20+35*5=195 btu/hr
Thanks Chris, this was very useful.
Hi Chris, Could you do an example for a 50 gallon gas water heater with 76,000 Btu/hr input? Is the Et term for baseline and proposed supposed to be prescriptive and design values, respectively?
EDIT: I found an example in the 90.1-2013 User's Manual. :-)