Requirements
Performance
Option 1. Daylight Measurement (2 points)
Achieve illuminance levels between 300 lux and 3,000 lux for at least 50% of the regularly occupied floor area. With furniture, fixtures, and equipment in place, measure illuminance levels as follows:- Measure at appropriate work plane height during any hour between 9 a.m. and 3 p.m.
- Take one measurement in any regularly occupied month, and take a second as indicated in Table 1.
- For spaces larger than 150 square feet (14 square meters), take measurements on a maximum 10-foot (3-meter) square grid.
- For spaces 150 square feet (14 square meters) or smaller, take measurements on a maximum 3-foot (900-millimeter) square grid.
- multiple lines of sight to vision glazing in different directions at least 90 degrees apart;
- views that include at least two of the following: (1) flora, fauna, or sky; (2) movement; and (3) objects at least 25 feet (7.5 meters) from the exterior of the glazing;
- unobstructed views located within the distance of three times the head height of the vision glazing; and
- views with a view factor of 3 or greater, as defined in “Windows and Offices; A Study of Office Worker Performance and the Indoor Environment.” Include in the calculations any permanent interior obstructions. Movable furniture and partitions may be excluded. Views into interior atria may be used to meet up to 30% of the required area. For the office portion of the building, meet the requirements above. For the bulk storage, sorting, and distribution portions of the building, Meet the requirements above for 25% of the regularly occupied floor area.
Table 1. Timing of measurements for illuminance
If first measurement is taken in … |
take second measurement in … |
---|---|
January |
May-September |
February |
June-October |
March |
June-July, November-December |
April |
August-December |
May |
September-January |
June |
October-February |
July |
November-March |
August |
December-April |
September |
December-January, May-June |
October |
February-June |
November |
March-July |
December |
April-August |
AND/OR
Option 2. Quality Views (2 points)
Achieve a direct line of sight to the outdoors via vision glazing for 50% of all regularly occupied floor area. View glazing in the contributing area must provide a clear image of the exterior, not obstructed by frits, fibers, patterned glazing, or added tints that distort color balance. Additionally, 50% of all regularly occupied floor area must have at least two of the following four kinds of views:Establishment
None.What does it cost?
Cost estimates for this credit
On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.
Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.
This information is also available in a full PDF download in The Cost of LEED v4 report.
Learn more about The Cost of LEED v4 »Frequently asked questions
What is the “view factor” and how do I calculate it?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |
Addenda
Documentation toolkit
The motherlode of cheat sheets
LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.
Get the inside scoop
Our editors have written a detailed analysis of nearly every LEED credit, and LEEDuser premium members get full access. We’ll tell you whether the credit is easy to accomplish or better left alone, and we provide insider tips on how to document it successfully.
© Copyright U.S. Green Building Council, Inc. All rights reserved.
Requirements
Performance
Option 1. Daylight Measurement (2 points)
Achieve illuminance levels between 300 lux and 3,000 lux for at least 50% of the regularly occupied floor area. With furniture, fixtures, and equipment in place, measure illuminance levels as follows:- Measure at appropriate work plane height during any hour between 9 a.m. and 3 p.m.
- Take one measurement in any regularly occupied month, and take a second as indicated in Table 1.
- For spaces larger than 150 square feet (14 square meters), take measurements on a maximum 10-foot (3-meter) square grid.
- For spaces 150 square feet (14 square meters) or smaller, take measurements on a maximum 3-foot (900-millimeter) square grid.
- multiple lines of sight to vision glazing in different directions at least 90 degrees apart;
- views that include at least two of the following: (1) flora, fauna, or sky; (2) movement; and (3) objects at least 25 feet (7.5 meters) from the exterior of the glazing;
- unobstructed views located within the distance of three times the head height of the vision glazing; and
- views with a view factor of 3 or greater, as defined in “Windows and Offices; A Study of Office Worker Performance and the Indoor Environment.” Include in the calculations any permanent interior obstructions. Movable furniture and partitions may be excluded. Views into interior atria may be used to meet up to 30% of the required area. For the office portion of the building, meet the requirements above. For the bulk storage, sorting, and distribution portions of the building, Meet the requirements above for 25% of the regularly occupied floor area.
Table 1. Timing of measurements for illuminance
If first measurement is taken in … |
take second measurement in … |
---|---|
January |
May-September |
February |
June-October |
March |
June-July, November-December |
April |
August-December |
May |
September-January |
June |
October-February |
July |
November-March |
August |
December-April |
September |
December-January, May-June |
October |
February-June |
November |
March-July |
December |
April-August |
AND/OR
Option 2. Quality Views (2 points)
Achieve a direct line of sight to the outdoors via vision glazing for 50% of all regularly occupied floor area. View glazing in the contributing area must provide a clear image of the exterior, not obstructed by frits, fibers, patterned glazing, or added tints that distort color balance. Additionally, 50% of all regularly occupied floor area must have at least two of the following four kinds of views:Establishment
None.In the end, LEED is all about documentation. LEEDuser’s Documentation Toolkit, for premium members only, saves you time and helps you avoid mistakes with:
- Calculators to help assess credit compliance.
- Tracking spreadsheets for materials purchases.
- Spreadsheets and forms to give to subs and other team members.
- Guidance documents on arcane LEED issues.
- Sample templates to help guide your narratives and LEED Online submissions.
- Examples of actual submissions from certified LEED projects.
What is the “view factor” and how do I calculate it?The answer to this question is available to LEEDuser premium members. Start a free trial » (If you're already a premium member, log in here.) |