Intent
To reduce ozone depletion and support early compliance with the Montreal Protocol while minimizing direct contributions to climate change.
Requirements
Option 1. No Refrigerants or Low-Impact Refrigerants (1 point)
Do not use refrigerants, or use only refrigerants (naturally occurring or synthetic) that have an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of less than 50. OROption 2. Calculation of Refrigerant Impact (1 point)
Select refrigerants that are used in heating, ventilating, air-conditioning, and refrigeration (HVAC&R) equipment to minimize or eliminate the emission of compounds that contribute to ozone depletion and climate change. The combination of all new and existing base building and tenant HVAC&R equipment that serve the project must comply with the following formula:IP units
|
SI units
|
Calculation definitions for |
Calculation definitions for |
---|---|
LCODP = [ODPr x (Lr x Life +Mr) x Rc]/Life |
LCODP = [ODPr x (Lr x Life +Mr) x Rc]/Life |
LCGWP = [GWPr x (Lr x Life +Mr) x Rc]/Life |
LCGWP = [GWPr x (Lr x Life +Mr) x Rc]/Life |
LCODP: Lifecycle Ozone Depletion Potential |
LCODP: Lifecycle Ozone Depletion Potential |
LCGWP: Lifecycle Direct Global Warming Potential |
LCGWP: Lifecycle Direct Global Warming Potential |
GWPr: Global Warming Potential of Refrigerant |
GWPr: Global Warming Potential of Refrigerant |
ODPr: Ozone Depletion Potential of Refrigerant |
ODPr: Ozone Depletion Potential of Refrigerant |
Lr: Refrigerant Leakage Rate |
Lr: Refrigerant Leakage Rate |
Mr: End-of-life Refrigerant Loss |
Mr: End-of-life Refrigerant Loss |
Rc: Refrigerant Charge |
Rc: Refrigerant Charge |
Life: Equipment Life |
Life: Equipment Life |
IP units |
|
SI units |
|
---|---|---|---|
∑ ( LCGWP + LCODP x 105 ) x Qunit |
≤ 100 |
∑ ( LCGWP + LCODP x 105 ) x Qunit |
≤ 13 |
Qtotal |
Qtotal |
Calculation definitions for |
Calculation definitions for |
---|---|
(IP units) | (SI units) |
Qunit = Gross AHRI rated cooling capacity of an individual HVAC or refrigeration unit (Tons) |
Qunit = Eurovent Certified cooling capacity of an individual HVAC or refrigeration unit (kW) |
Qtotal = Total gross AHRI rated cooling capacity of all HVAC or refrigeration |
Qtotal = Total Eurovent Certified cooling capacity of all HVAC or refrigeration (kW) |
- Use only non-ozone-depleting refrigerants.
- Achieve an average HFC refrigerant charge of no more than 1.75 pounds of refrigerant per 1,000 Btu/h (2.72 grams of refrigerant per kW) total evaporator cooling load.
- Achieve a store-wide annual refrigerant emissions rate of no more than 15%.
What does it cost?
Cost estimates for this credit
On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.
Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.
This information is also available in a full PDF download in The Cost of LEED v4 report.
Learn more about The Cost of LEED v4 »Frequently asked questions
See all forum discussions about this credit »Documentation toolkit
The motherlode of cheat sheets
LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.
Get the inside scoop
Our editors have written a detailed analysis of nearly every LEED credit, and LEEDuser premium members get full access. We’ll tell you whether the credit is easy to accomplish or better left alone, and we provide insider tips on how to document it successfully.

© Copyright U.S. Green Building Council, Inc. All rights reserved.
Intent
To reduce ozone depletion and support early compliance with the Montreal Protocol while minimizing direct contributions to climate change.
Requirements
Option 1. No Refrigerants or Low-Impact Refrigerants (1 point)
Do not use refrigerants, or use only refrigerants (naturally occurring or synthetic) that have an ozone depletion potential (ODP) of zero and a global warming potential (GWP) of less than 50. OROption 2. Calculation of Refrigerant Impact (1 point)
Select refrigerants that are used in heating, ventilating, air-conditioning, and refrigeration (HVAC&R) equipment to minimize or eliminate the emission of compounds that contribute to ozone depletion and climate change. The combination of all new and existing base building and tenant HVAC&R equipment that serve the project must comply with the following formula:IP units
|
SI units
|
Calculation definitions for |
Calculation definitions for |
---|---|
LCODP = [ODPr x (Lr x Life +Mr) x Rc]/Life |
LCODP = [ODPr x (Lr x Life +Mr) x Rc]/Life |
LCGWP = [GWPr x (Lr x Life +Mr) x Rc]/Life |
LCGWP = [GWPr x (Lr x Life +Mr) x Rc]/Life |
LCODP: Lifecycle Ozone Depletion Potential |
LCODP: Lifecycle Ozone Depletion Potential |
LCGWP: Lifecycle Direct Global Warming Potential |
LCGWP: Lifecycle Direct Global Warming Potential |
GWPr: Global Warming Potential of Refrigerant |
GWPr: Global Warming Potential of Refrigerant |
ODPr: Ozone Depletion Potential of Refrigerant |
ODPr: Ozone Depletion Potential of Refrigerant |
Lr: Refrigerant Leakage Rate |
Lr: Refrigerant Leakage Rate |
Mr: End-of-life Refrigerant Loss |
Mr: End-of-life Refrigerant Loss |
Rc: Refrigerant Charge |
Rc: Refrigerant Charge |
Life: Equipment Life |
Life: Equipment Life |
IP units |
|
SI units |
|
---|---|---|---|
∑ ( LCGWP + LCODP x 105 ) x Qunit |
≤ 100 |
∑ ( LCGWP + LCODP x 105 ) x Qunit |
≤ 13 |
Qtotal |
Qtotal |
Calculation definitions for |
Calculation definitions for |
---|---|
(IP units) | (SI units) |
Qunit = Gross AHRI rated cooling capacity of an individual HVAC or refrigeration unit (Tons) |
Qunit = Eurovent Certified cooling capacity of an individual HVAC or refrigeration unit (kW) |
Qtotal = Total gross AHRI rated cooling capacity of all HVAC or refrigeration |
Qtotal = Total Eurovent Certified cooling capacity of all HVAC or refrigeration (kW) |
- Use only non-ozone-depleting refrigerants.
- Achieve an average HFC refrigerant charge of no more than 1.75 pounds of refrigerant per 1,000 Btu/h (2.72 grams of refrigerant per kW) total evaporator cooling load.
- Achieve a store-wide annual refrigerant emissions rate of no more than 15%.