LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To minimize indoor demand for water through high-efficiency fixtures and fittings.

Requirements

Case 1. Single family

Projects that install fixtures consuming more than 2.5 gallons per minute (9.5 liters per minute) per shower compartment must use WE Credit Total Water Use.

Each lavatory faucet or faucet aerator must be WaterSense labeled. The average rated flow volume across all lavatory faucets must not exceed 1.5 gallons per minute (5.6 liters per minute) for 1 point or 1.0 gallons per minute (3.7 liters per minute) for 2 points.

Each showerhead fixture and fitting must be WaterSense labeled. The average rated flow volume per shower compartment must not exceed 1.75 gallons per minute (6.6 liters per minute) for 1 point or 1.5 gallons per minute (5.6 liters per minute) for 2 points.

Each toilet fixture and fitting must be WaterSense labeled. The average rated flush volume across all toilets must not exceed 1.1 gallons (4.1 liters) per flush (1 point).

Each clothes washer must be ENERGY STAR qualified or performance equivalent for projects outside the U.S. (1 point)

The water pressure in the house must not exceed 60 pounds per square inch (414 kPa), with no detectable water leaks.

For projects outside the United States, a local equivalent to WaterSense may be used.

Case 2. Multifamily and Midrise

Meet the above requirements for all in-unit spaces and non-unit (residential-associated and nonresidential) spaces. Multifamily and midrise projects are exempt from the water pressure testing criterion. No additional credit is awarded if the fixtures and fittings in non-unit spaces are more efficient than those of in-unit spaces.

See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To minimize indoor demand for water through high-efficiency fixtures and fittings.

Requirements

Case 1. Single family

Projects that install fixtures consuming more than 2.5 gallons per minute (9.5 liters per minute) per shower compartment must use WE Credit Total Water Use.

Each lavatory faucet or faucet aerator must be WaterSense labeled. The average rated flow volume across all lavatory faucets must not exceed 1.5 gallons per minute (5.6 liters per minute) for 1 point or 1.0 gallons per minute (3.7 liters per minute) for 2 points.

Each showerhead fixture and fitting must be WaterSense labeled. The average rated flow volume per shower compartment must not exceed 1.75 gallons per minute (6.6 liters per minute) for 1 point or 1.5 gallons per minute (5.6 liters per minute) for 2 points.

Each toilet fixture and fitting must be WaterSense labeled. The average rated flush volume across all toilets must not exceed 1.1 gallons (4.1 liters) per flush (1 point).

Each clothes washer must be ENERGY STAR qualified or performance equivalent for projects outside the U.S. (1 point)

The water pressure in the house must not exceed 60 pounds per square inch (414 kPa), with no detectable water leaks.

For projects outside the United States, a local equivalent to WaterSense may be used.

Case 2. Multifamily and Midrise

Meet the above requirements for all in-unit spaces and non-unit (residential-associated and nonresidential) spaces. Multifamily and midrise projects are exempt from the water pressure testing criterion. No additional credit is awarded if the fixtures and fittings in non-unit spaces are more efficient than those of in-unit spaces.

See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Mid-Rise-v4 WEc2