Log in
LEED v4
Homes Mid-Rise
Indoor Environmental Quality
Balancing of heating and cooling distribution systems

LEED CREDIT

Mid-Rise-v4 EQc3: Balancing of heating and cooling distribution systems 1-3 points

LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To improve thermal comfort and energy performance by ensuring appropriate distribution of space heating and cooling in the home.

Requirements

Case 1. Forced-Air Systems
Option 1. Multiple Zones (1 point)

Install a system with at least two space-conditioning zones with independent thermostatic controls. In houses with both a heating system and a cooling system, each must have at least two zones.

Single-family houses with less than 800 square feet (74 square meters) of conditioned floor area and multifamily buildings whose average unit size is less than 1,200 square feet (110 square meters) automatically meet the requirements of this credit.

AND/OR

Option 2. Supply Air-Flow Testing (1 point)

Have the total supply air-flow rates in each room tested using a flow hood with doors closed, or another acceptable method, per RESNET or ACCA Quality Installation Specifications.

Supply air-flow rates must be within +/- 20% (or +/- 25 cfm or 11 lps) of calculated values from ACCA Manual J.

Test multirate or multispeed HVAC systems at the rate for which they were designed. Supply air-flow requirements must meet the higher of the cooling or heating designed air flow for each room.

Ductless systems qualify for this credit.

Option 3. Pressure Balancing (1 point)

For each bedroom, demonstrate a pressure difference of less than 3 Pa (0.012 inch w.c.) with respect to the main body of the house when doors are closed and the air handler is operating on highest speed.

Case 2. Radiative Systems
Option 1. Multiple Zones (1 point)

Install an HVAC system with at least two zones with independent thermostat controls. Each zone must have a separate loop and separate pump controlled automatically by a thermostat control. For HVAC systems with radiators, see Option 2.

Houses with less than 800 square feet (74 square meters) of conditioned floor area and multifamily buildings whose average unit size is less than 1,200 square feet (110 square meters) automatically meet the requirements of this credit.

AND/OR

Option 2. Room-by-Room Controls (2 points)
Design the HVAC system with room-by-room thermostatic controls, such as flow-control valves on every radiator.
See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To improve thermal comfort and energy performance by ensuring appropriate distribution of space heating and cooling in the home.

Requirements

Case 1. Forced-Air Systems
Option 1. Multiple Zones (1 point)

Install a system with at least two space-conditioning zones with independent thermostatic controls. In houses with both a heating system and a cooling system, each must have at least two zones.

Single-family houses with less than 800 square feet (74 square meters) of conditioned floor area and multifamily buildings whose average unit size is less than 1,200 square feet (110 square meters) automatically meet the requirements of this credit.

AND/OR

Option 2. Supply Air-Flow Testing (1 point)

Have the total supply air-flow rates in each room tested using a flow hood with doors closed, or another acceptable method, per RESNET or ACCA Quality Installation Specifications.

Supply air-flow rates must be within +/- 20% (or +/- 25 cfm or 11 lps) of calculated values from ACCA Manual J.

Test multirate or multispeed HVAC systems at the rate for which they were designed. Supply air-flow requirements must meet the higher of the cooling or heating designed air flow for each room.

Ductless systems qualify for this credit.

Option 3. Pressure Balancing (1 point)

For each bedroom, demonstrate a pressure difference of less than 3 Pa (0.012 inch w.c.) with respect to the main body of the house when doors are closed and the air handler is operating on highest speed.

Case 2. Radiative Systems
Option 1. Multiple Zones (1 point)

Install an HVAC system with at least two zones with independent thermostat controls. Each zone must have a separate loop and separate pump controlled automatically by a thermostat control. For HVAC systems with radiators, see Option 2.

Houses with less than 800 square feet (74 square meters) of conditioned floor area and multifamily buildings whose average unit size is less than 1,200 square feet (110 square meters) automatically meet the requirements of this credit.

AND/OR

Option 2. Room-by-Room Controls (2 points)
Design the HVAC system with room-by-room thermostatic controls, such as flow-control valves on every radiator.
See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Mid-Rise-v4 EQc3