Log in
LEED v4
Homes Mid-Rise
Indoor Environmental Quality
Contaminant control

LEED CREDIT

Mid-Rise-v4 EQc2: Contaminant control 0.5-2 points

LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To reduce occupants’ exposure to indoor airborne contaminants through source control and removal.

Requirements

Option 1. Walk-off Mats (0.5 point)

At each unit’s primary entryway from the outdoors, design and install a permanent walk-off mat that is at least 4 feet (1.2 meters) long and allows access for cleaning (e.g., grating with catch basin).

For regularly used common exterior entryways in multifamily buildings, install permanent systems that are at least 10 feet (3 meters) long in the primary direction of travel to capture dirt and particulates. Acceptable entryway systems include permanently installed grates, grilles, and slotted surfaces that allow for cleaning underneath. Roll-out mats are acceptable only if maintained on a weekly basis by a contracted service organization.

AND/OR

Option 2. Shoe Removal and Storage (0.5 point)

In each unit, design a shoe removal and storage space near the entryway, separated from living areas. This space must be a permanent architectural feature, it may not have wall-to-wall carpeting, and it must be large enough to accommodate a bench and at least two pairs of shoes per bedroom.

AND/OR

Option 3. Preoccupancy flush (0.5 point)

The Preoccupancy Flush can be awarded if the requirements are only met for all in-unit spaces.
At installation, seal all permanent ducts and vents to minimize contamination from construction. Remove seals after all phases of construction are completed.

After construction ends and before occupancy, flush the home with fresh air, according to the following guidelines:

  • Remove any dust and debris from ducts.
  • Flush the entire home, keeping all interior doors open for 48 hours; the hours may be nonconsecutive if necessary.
  • Keep all windows open and run a fan (e.g., HVAC system fan) continuously, or flush the home with all HVAC fans and exhaust fans operating continuously at the highest flow rate.

For multifamily buildings, the requirements apply only to all in-unit spaces.

AND/OR

Option 4. Air Testing (1 point)

After construction ends and before occupancy, but under ventilation conditions typical for occupancy, conduct baseline indoor air quality testing using protocols consistent with the methods listed in Table 1. Project teams must follow either the Use current versions of ASTM standard methods, EPA compendium methods, or ISO methods, as indicated. Laboratories that conduct the tests for chemical analysis of formaldehyde and volatile organic compounds must be accredited under ISO/IEC 17025 for the test methods they use.

Demonstrate that contaminants do not exceed concentration levels listed in Table 1.

Table 1. Maximum concentration levels, by contaminant and testing method

Contaminant Maximum concentration Maximum concentration (Healthcare only) ASTM and U.S. EPA methods ISO method
Formaldehyde 27 ppb 16.3 ppb ASTM D5197; EPA TO-11 or EPA Compendium Method IP-6 ISO 16000-3
Particulates (PM10 for all buildings; PM2.5 for buildings in EPA nonattainment areas) PM10: 50 micrograms per cubic meter
PM2.5: 15 micrograms per cubic meter
20 micrograms per cubic meter EPA Compendium Method IP-10 ISO 7708
Ozone (for buildings in EPA nonattainment areas) 0.075 ppm 0.075 ppm ASTM D5149 - 02 ISO 13964
Total volatile organic compounds (TVOCs) 500 micrograms per cubic meter 200 micrograms per cubic meter EPA TO-1, TO-15, TO-17, or EPA Compendium Method IP-1 ISO 16000-6
Target chemicals listed in CDPH Standard Method v1.1, Table 4-1, except formaldehyde CDPH Standard Method v1.1–2010, Allowable Concentrations, Table 4-1 CDPH Standard Method v1.1–2010, Allowable Concentrations, Table 4-1 ASTM D5197; EPA TO-1, TO-15, TO-17, or EPA Compendium Method ISO 16000-3,  16000-6
Carbon monoxide (CO) 9 ppm; no more than 2 ppm above outdoor levels 9 ppm; no more than 2 ppm above outdoor levels EPA Compendium Method IP-3 ISO 4224

ppb = parts per billion; ppm = parts per million; μg/cm = micrograms per cubic meter

Conduct all measurements before occupancy but during normal occupied hours, with the building ventilation system started at the normal daily start time and operated at the minimum outside air flow rate for the occupied mode throughout the test.

The number of sampling locations depends on the size of the building and number of ventilation systems but must include the entire building and all representative situations. Include areas with the least ventilation and greatest presumed source strength.

Collect air samples between 3 and 6 feet (900 and 1 800 millimeters) from the floor to represent the breathing zone of occupants over a minimum four-hour period.

Measure particulate concentrations by a gravimetric method. Hand-held or real-time instruments are not acceptable unless they are calibrated on site against the standard gravimetric method.

For each sampling point where the concentration exceeds the limit, take corrective action and retest for the noncompliant contaminants at the same sampling points. Repeat until all requirements are met.

Refer to CA Section 01350, Appendix B, New Single-Family Residence Scenario, for air-testing guidance.

See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Addenda

10/2/2017Updated: 10/23/2017
Rating System Correction
Description of change:
Revise Table 1 as follows:

1. Remove TO-15 from "ASTM and U.S. EPA methods" column

2. Add the full list of target chemicals, except formaldehyde, from CDPH Standard Method v1.1 in place of the single row (Target chemicals listed in CDPH Standard Method v1.1, Table 4.1, except formaldehyde) and revise the Maximum concentrations from CDPH Standard Method v1.1 2010, Allowable Concentrations, Table 4-1 with the Cal/EPA OEHHA full CREL in effect on June 2014.

3. reformat table for clarity
Campus Applicable
No
Internationally Applicable:
No
See all forum discussions about this credit »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To reduce occupants’ exposure to indoor airborne contaminants through source control and removal.

Requirements

Option 1. Walk-off Mats (0.5 point)

At each unit’s primary entryway from the outdoors, design and install a permanent walk-off mat that is at least 4 feet (1.2 meters) long and allows access for cleaning (e.g., grating with catch basin).

For regularly used common exterior entryways in multifamily buildings, install permanent systems that are at least 10 feet (3 meters) long in the primary direction of travel to capture dirt and particulates. Acceptable entryway systems include permanently installed grates, grilles, and slotted surfaces that allow for cleaning underneath. Roll-out mats are acceptable only if maintained on a weekly basis by a contracted service organization.

AND/OR

Option 2. Shoe Removal and Storage (0.5 point)

In each unit, design a shoe removal and storage space near the entryway, separated from living areas. This space must be a permanent architectural feature, it may not have wall-to-wall carpeting, and it must be large enough to accommodate a bench and at least two pairs of shoes per bedroom.

AND/OR

Option 3. Preoccupancy flush (0.5 point)

The Preoccupancy Flush can be awarded if the requirements are only met for all in-unit spaces.
At installation, seal all permanent ducts and vents to minimize contamination from construction. Remove seals after all phases of construction are completed.

After construction ends and before occupancy, flush the home with fresh air, according to the following guidelines:

  • Remove any dust and debris from ducts.
  • Flush the entire home, keeping all interior doors open for 48 hours; the hours may be nonconsecutive if necessary.
  • Keep all windows open and run a fan (e.g., HVAC system fan) continuously, or flush the home with all HVAC fans and exhaust fans operating continuously at the highest flow rate.

For multifamily buildings, the requirements apply only to all in-unit spaces.

AND/OR

Option 4. Air Testing (1 point)

After construction ends and before occupancy, but under ventilation conditions typical for occupancy, conduct baseline indoor air quality testing using protocols consistent with the methods listed in Table 1. Project teams must follow either the Use current versions of ASTM standard methods, EPA compendium methods, or ISO methods, as indicated. Laboratories that conduct the tests for chemical analysis of formaldehyde and volatile organic compounds must be accredited under ISO/IEC 17025 for the test methods they use.

Demonstrate that contaminants do not exceed concentration levels listed in Table 1.

Table 1. Maximum concentration levels, by contaminant and testing method

Contaminant Maximum concentration Maximum concentration (Healthcare only) ASTM and U.S. EPA methods ISO method
Formaldehyde 27 ppb 16.3 ppb ASTM D5197; EPA TO-11 or EPA Compendium Method IP-6 ISO 16000-3
Particulates (PM10 for all buildings; PM2.5 for buildings in EPA nonattainment areas) PM10: 50 micrograms per cubic meter
PM2.5: 15 micrograms per cubic meter
20 micrograms per cubic meter EPA Compendium Method IP-10 ISO 7708
Ozone (for buildings in EPA nonattainment areas) 0.075 ppm 0.075 ppm ASTM D5149 - 02 ISO 13964
Total volatile organic compounds (TVOCs) 500 micrograms per cubic meter 200 micrograms per cubic meter EPA TO-1, TO-15, TO-17, or EPA Compendium Method IP-1 ISO 16000-6
Target chemicals listed in CDPH Standard Method v1.1, Table 4-1, except formaldehyde CDPH Standard Method v1.1–2010, Allowable Concentrations, Table 4-1 CDPH Standard Method v1.1–2010, Allowable Concentrations, Table 4-1 ASTM D5197; EPA TO-1, TO-15, TO-17, or EPA Compendium Method ISO 16000-3,  16000-6
Carbon monoxide (CO) 9 ppm; no more than 2 ppm above outdoor levels 9 ppm; no more than 2 ppm above outdoor levels EPA Compendium Method IP-3 ISO 4224

ppb = parts per billion; ppm = parts per million; μg/cm = micrograms per cubic meter

Conduct all measurements before occupancy but during normal occupied hours, with the building ventilation system started at the normal daily start time and operated at the minimum outside air flow rate for the occupied mode throughout the test.

The number of sampling locations depends on the size of the building and number of ventilation systems but must include the entire building and all representative situations. Include areas with the least ventilation and greatest presumed source strength.

Collect air samples between 3 and 6 feet (900 and 1 800 millimeters) from the floor to represent the breathing zone of occupants over a minimum four-hour period.

Measure particulate concentrations by a gravimetric method. Hand-held or real-time instruments are not acceptable unless they are calibrated on site against the standard gravimetric method.

For each sampling point where the concentration exceeds the limit, take corrective action and retest for the noncompliant contaminants at the same sampling points. Repeat until all requirements are met.

Refer to CA Section 01350, Appendix B, New Single-Family Residence Scenario, for air-testing guidance.

See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Mid-Rise-v4 EQc2