Log in
LEED v2008
Homes
Indoor Environmental Quality
Acoustic comfort

LEED CREDIT

Homes-v2008 EQpc47: Acoustic Comfort 1 point

LEEDuser’s viewpoint

Frank advice from LEED experts

LEED is changing all the time, and every project is unique. Even seasoned professionals can miss a critical detail and lose a credit or even a prerequisite at the last minute. Our expert advice guides our LEEDuser Premium members and saves you valuable time.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

These requirements only apply to “acoustically sensitive” rooms, such as bedrooms, dining rooms, living rooms, and studies. (“Acoustically insensitive” rooms include bathrooms, kitchens, and hallways.) Projects may also implement the measures throughout the entire home.
Option 1. Prescriptive noise reduction methods.
Meet all of the following requirements:
  1. Mechanical systems must meet the following requirements:
    • Continuous ventilation fans shall have a maximum sound rating of 0.7 sones. Intermittent fans shall have a maximum sound rating of 1.5 sones, unless their maximum rated airflow exceeds 400 cfm. HVAC air handlers and remote-mounted fans are exempted, if the fans are mounted outside the habitable spaces, bathrooms, and hallways, and if there is at least 4 feet of ductwork between the fan and the intake grill.
    • Meet the following best-practice HVAC installation measures:
      • Ducts are securely attached (no loose connections between sections of ductwork).
      • The fan housing is securely anchored.
      • The damper flap closes fully, with no visible airspaces around the flap.
  2. For projects that are less than a half a mile away from any significant noise source such as (but not limited to) aircraft over-flights, highways, trains, and industry, exterior assemblies must include:
    • Exterior windows and doors must have a minimum STC rating of 35.
    • All exterior wall penetrations must be sealed with acoustical sealant,
    • and/or otherwise treated for sound control (e.g. lined elbows on vents, lined exterior ducts where feasible).
  3. Attached single family homes and multi-family homes must also meet the following:
    • Party walls must have a minimum STC rating of 55.
    • All party wall penetrations must be sealed with acoustical sealant
      • Floor/ceiling assemblies must have a minimum STC and IIC rating of 55.
AND/OR
Option 2. Performance-based compliance requirements
Meet all of the following. The tested levels must be met in the acoustically sensitive room that is considered the worst case condition.
  1. The maximum background noise level in the home or unit due to exterior noise sources cannot exceed 40 dBA, based on the peak hour Leq.
  2. The maximum background noise level in the home or unit due to interior noise sources (HVAC systems, lighting, and other building services operating simultaneously) shall not exceed 40 dBA, based on the peak Leq.
  3. Party walls must have a minimum NIC rating of 50.
  4. Floor-ceiling assemblies between units must have a minimum NIC and FIIC rating of 50.
Ductless systems qualify for this credit.

General Pilot Documentation Requirements

Register for the pilot credit Credits 1-14 Credits 15-27 Credits 28-42 Credits 43-56 Credits 57-67 Credits 68-82 Credits 83--96
LEED for Homes Review Process
LEED for Homes projects: When complete, submit documentation here.
See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

Get the inside scoop

Our editors have written a detailed analysis of nearly every LEED credit, and LEEDuser premium members get full access. We’ll tell you whether the credit is easy to accomplish or better left alone, and we provide insider tips on how to document it successfully.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

These requirements only apply to “acoustically sensitive” rooms, such as bedrooms, dining rooms, living rooms, and studies. (“Acoustically insensitive” rooms include bathrooms, kitchens, and hallways.) Projects may also implement the measures throughout the entire home.
Option 1. Prescriptive noise reduction methods.
Meet all of the following requirements:
  1. Mechanical systems must meet the following requirements:
    • Continuous ventilation fans shall have a maximum sound rating of 0.7 sones. Intermittent fans shall have a maximum sound rating of 1.5 sones, unless their maximum rated airflow exceeds 400 cfm. HVAC air handlers and remote-mounted fans are exempted, if the fans are mounted outside the habitable spaces, bathrooms, and hallways, and if there is at least 4 feet of ductwork between the fan and the intake grill.
    • Meet the following best-practice HVAC installation measures:
      • Ducts are securely attached (no loose connections between sections of ductwork).
      • The fan housing is securely anchored.
      • The damper flap closes fully, with no visible airspaces around the flap.
  2. For projects that are less than a half a mile away from any significant noise source such as (but not limited to) aircraft over-flights, highways, trains, and industry, exterior assemblies must include:
    • Exterior windows and doors must have a minimum STC rating of 35.
    • All exterior wall penetrations must be sealed with acoustical sealant,
    • and/or otherwise treated for sound control (e.g. lined elbows on vents, lined exterior ducts where feasible).
  3. Attached single family homes and multi-family homes must also meet the following:
    • Party walls must have a minimum STC rating of 55.
    • All party wall penetrations must be sealed with acoustical sealant
      • Floor/ceiling assemblies must have a minimum STC and IIC rating of 55.
AND/OR
Option 2. Performance-based compliance requirements
Meet all of the following. The tested levels must be met in the acoustically sensitive room that is considered the worst case condition.
  1. The maximum background noise level in the home or unit due to exterior noise sources cannot exceed 40 dBA, based on the peak hour Leq.
  2. The maximum background noise level in the home or unit due to interior noise sources (HVAC systems, lighting, and other building services operating simultaneously) shall not exceed 40 dBA, based on the peak Leq.
  3. Party walls must have a minimum NIC rating of 50.
  4. Floor-ceiling assemblies between units must have a minimum NIC and FIIC rating of 50.
Ductless systems qualify for this credit.

General Pilot Documentation Requirements

Register for the pilot credit Credits 1-14 Credits 15-27 Credits 28-42 Credits 43-56 Credits 57-67 Credits 68-82 Credits 83--96
LEED for Homes Review Process
LEED for Homes projects: When complete, submit documentation here.
See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Homes-v2008 EQpc47