All occupied spaces in naturally ventilated buildings require the installation of at least one CO2 sensor. The number of CO2 sensors depends on the project’s design and should be calculated by the mechanical engineer. Projects can use one CO2 sensor for m

All occupied spaces in naturally ventilated buildings require the installation of at least one CO2 sensor. The number of CO2 sensors depends on the project’s design and should be calculated by the mechanical engineer. Projects can use one CO2 sensor for multiple spaces only if the project is ventilated by an approved “engineered natural ventilation system” according to ASHRAE 62.1-2004 requirements and if it does not require occupant intervention. This type of ventilation system connects adjacent spaces via air pathways that utilize the stack effect, or passive air movement from openings at a lower level than the point of exhaust. A single CO2 sensor can be used in these connected spaces. To meet the credit requirement, an engineer must demonstrate that the natural ventilation system can maintain adequate ventilation rates.