As required in LEED Interpretation 10044, all equipment classified as eligible by ENERGY STAR must be included in the calculations. Equipment that is procured within two years of the effective date of the first (i.e. Version 1.0) ENERGY STAR product specification for that equipment category may be included or excluded at the discretion of the project team; however, all equipment within that category must be included or excluded consistently. Refer to the ENERGY STAR product specification(s) for the effective date.
Calculations may be completed using either the rated power OR the average annual power consumption, but the metric selected must be consistent for all equipment included in the calculations. For the purposes of demonstrating equivalency to the ENERGY STAR product specification by average annual power consumption, equipment purchased may use no more than the average annual energy consumption of the equivalent ENERGY STAR-qualified product as determined by the appropriate ENERGY STAR savings calculator. The average annual power consumption for purchased equipment may be demonstrated by manufacturer documentation or calculated from actual equipment operating data and anticipated use profiles.
For Uninterruptible Power Supply (UPS) equipment:
If using the rated power methodology, the UPS “rated power” for the LEED Calculation may optionally be derated to 35% of the UPS Rated Output Power to more accurately reflect the relative energy usage associated with UPS equipment compared to other Energy Star equipment.
If using the average annual power consumption methodology, the UPS average annual power consumption (in units of kWh/year) shall be calculated as:
UPS Annual Power Consumption = 6,600 x Power x (1-EffAVGMIN)
Where:
Power is the UPS Rated Output Power in units of kW.
EffAVGMIN is determined consistently with the ENERGY STAR® Program Requirements, or 93.7% if unknown.
For projects located outside of the United States, the following approved standards may be used in place of ENERGY STAR for equipment categories covered by these standards: EU ENERGY STAR, TCO, Blue Angel. Additionally, equipment classified as eligible by ENERGY STAR but not ENERGY STAR-qualified may be deemed equivalent if the equipment has been labeled by a local energy label and has been rated by the labeling program to use no more than the average annual energy consumption of the equivalent ENERGY STAR-qualified product as determined by the appropriate ENERGY STAR savings calculator.
Updated 01/05/18 for rating system version applicability and to provide additional calculation options for Uninterruptible Power Supply equipment.