BASELINE 0 DEGREES: SLincoln Prop 042710 DOE-2.2-47h2 4/20/2011 16:08:38 BDL RUN 3 REPORT- BEPS Building Energy Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY MBTU 1100.3 0.0 759.2 332.3 642.1 0.0 26.2 313.2 0.0 817.2 0.0 43.1 4033.5 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1147.7 0.0 0.0 0.0 0.0 0.0 0.0 1365.6 0.0 2513.3 ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======== MBTU 1100.3 0.0 759.2 1480.0 642.1 0.0 26.2 313.2 0.0 817.2 1365.6 43.1 6546.8 TOTAL SITE ENERGY 6546.78 MBTU 67.6 KBTU/SQFT-YR GROSS-AREA 67.6 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 14613.81 MBTU 151.0 KBTU/SQFT-YR GROSS-AREA 151.0 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.49 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 120 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 98 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. SLincoln Prop 042710 DOE-2.2-47h2 4/20/2011 16:08:38 BDL RUN 3 REPORT- BEPU Building Utility Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY KWH 322391. 0. 222441. 97360. 188127. 0. 7677. 91758. 0. 239440. 0. 12624. 1181819. FM1 NATURAL-GAS THERM 0. 0. 0. 11477. 0. 0. 0. 0. 0. 0. 13656. 0. 25133. TOTAL ELECTRICITY 1181819. KWH 12.210 KWH /SQFT-YR GROSS-AREA 12.210 KWH /SQFT-YR NET-AREA TOTAL NATURAL-GAS 25133. THERM 0.260 THERM /SQFT-YR GROSS-AREA 0.260 THERM /SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.49 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 120 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 98 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. SLincoln Prop 042710 DOE-2.2-47h2 4/20/2011 16:08:38 BDL RUN 3 REPORT- ES-D Energy Cost Summary WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? -------------------------------- ---------------- ----------- ------------------- ---------- ---------- --------- Custom Elec Rate ELECTRICITY EM1 1181819. KWH 100016. 0.0846 YES Custom Gas Rate NATURAL-GAS FM1 25133. THERM 17833. 0.7095 YES ========== 117849. ENERGY COST/GROSS BLDG AREA: 1.22 ENERGY COST/NET BLDG AREA: 1.22 BASELINE 90 DEGREES: REPORT- BEPS Building Energy Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY MBTU 1100.3 0.0 759.2 316.5 650.0 0.0 26.2 323.8 0.0 791.8 0.0 43.1 4010.9 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1167.6 0.0 0.0 0.0 0.0 0.0 0.0 1365.7 0.0 2533.3 ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======== MBTU 1100.3 0.0 759.2 1484.1 650.0 0.0 26.2 323.8 0.0 791.8 1365.7 43.1 6544.2 TOTAL SITE ENERGY 6544.18 MBTU 67.6 KBTU/SQFT-YR GROSS-AREA 67.6 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 14566.03 MBTU 150.5 KBTU/SQFT-YR GROSS-AREA 150.5 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.48 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 115 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 102 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- BEPU Building Utility Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY KWH 322391. 0. 222441. 92742. 190463. 0. 7677. 94872. 0. 231990. 0. 12624. 1175199. FM1 NATURAL-GAS THERM 0. 0. 0. 11676. 0. 0. 0. 0. 0. 0. 13657. 0. 25333. TOTAL ELECTRICITY 1175199. KWH 12.142 KWH /SQFT-YR GROSS-AREA 12.142 KWH /SQFT-YR NET-AREA TOTAL NATURAL-GAS 25333. THERM 0.262 THERM /SQFT-YR GROSS-AREA 0.262 THERM /SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.48 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 115 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 102 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? -------------------------------- ---------------- ----------- ------------------- ---------- ---------- --------- Custom Elec Rate ELECTRICITY EM1 1175199. KWH 99108. 0.0843 YES Custom Gas Rate NATURAL-GAS FM1 25333. THERM 17973. 0.7095 YES ========== 117081. ENERGY COST/GROSS BLDG AREA: 1.21 ENERGY COST/NET BLDG AREA: 1.21 BASELINE 180 DEGREES: REPORT- BEPS Building Energy Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY MBTU 1100.3 0.0 759.2 340.4 671.8 0.0 26.2 319.3 0.0 808.3 0.0 43.1 4068.7 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1169.4 0.0 0.0 0.0 0.0 0.0 0.0 1366.2 0.0 2535.7 ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======== MBTU 1100.3 0.0 759.2 1509.9 671.8 0.0 26.2 319.3 0.0 808.3 1366.2 43.1 6604.3 TOTAL SITE ENERGY 6604.33 MBTU 68.2 KBTU/SQFT-YR GROSS-AREA 68.2 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 14741.64 MBTU 152.3 KBTU/SQFT-YR GROSS-AREA 152.3 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.48 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 115 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 102 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- BEPU Building Utility Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY KWH 322391. 0. 222441. 99743. 196843. 0. 7677. 93567. 0. 236828. 0. 12624. 1192115. FM1 NATURAL-GAS THERM 0. 0. 0. 11694. 0. 0. 0. 0. 0. 0. 13662. 0. 25357. TOTAL ELECTRICITY 1192115. KWH 12.316 KWH /SQFT-YR GROSS-AREA 12.316 KWH /SQFT-YR NET-AREA TOTAL NATURAL-GAS 25357. THERM 0.262 THERM /SQFT-YR GROSS-AREA 0.262 THERM /SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.48 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 115 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 102 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? -------------------------------- ---------------- ----------- ------------------- ---------- ---------- --------- Custom Elec Rate ELECTRICITY EM1 1192115. KWH 100792. 0.0845 YES Custom Gas Rate NATURAL-GAS FM1 25357. THERM 17990. 0.7095 YES ========== 118781. ENERGY COST/GROSS BLDG AREA: 1.23 ENERGY COST/NET BLDG AREA: 1.23 BASELINE 270 DEGREES: REPORT- BEPS Building Energy Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY MBTU 1100.3 0.0 759.2 341.7 627.1 0.0 26.2 307.6 0.0 843.9 0.0 43.1 4049.1 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1150.7 0.0 0.0 0.0 0.0 0.0 0.0 1366.1 0.0 2516.8 ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======== MBTU 1100.3 0.0 759.2 1492.4 627.1 0.0 26.2 307.6 0.0 843.9 1366.1 43.1 6565.9 TOTAL SITE ENERGY 6565.94 MBTU 67.8 KBTU/SQFT-YR GROSS-AREA 67.8 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 14664.14 MBTU 151.5 KBTU/SQFT-YR GROSS-AREA 151.5 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.49 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 120 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 98 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- BEPU Building Utility Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY KWH 322391. 0. 222441. 100105. 183746. 0. 7677. 90129. 0. 247271. 0. 12624. 1186385. FM1 NATURAL-GAS THERM 0. 0. 0. 11507. 0. 0. 0. 0. 0. 0. 13661. 0. 25168. TOTAL ELECTRICITY 1186385. KWH 12.257 KWH /SQFT-YR GROSS-AREA 12.257 KWH /SQFT-YR NET-AREA TOTAL NATURAL-GAS 25168. THERM 0.260 THERM /SQFT-YR GROSS-AREA 0.260 THERM /SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.49 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 120 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 98 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? -------------------------------- ---------------- ----------- ------------------- ---------- ---------- --------- Custom Elec Rate ELECTRICITY EM1 1186385. KWH 99843. 0.0842 YES Custom Gas Rate NATURAL-GAS FM1 25168. THERM 17858. 0.7095 YES ========== 117700. ENERGY COST/GROSS BLDG AREA: 1.22 ENERGY COST/NET BLDG AREA: 1.22 PROPOSED: SLincoln Prop 042710 DOE-2.2-47h2 4/21/2011 14:35:51 BDL RUN 1 REPORT- BEPS Building Energy Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY MBTU 514.2 0.0 674.5 294.7 224.9 0.0 32.1 205.9 0.0 21.5 0.0 16.0 1983.8 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1358.1 0.0 0.0 0.0 0.0 0.0 0.0 1060.3 0.0 2418.4 ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======= ======== MBTU 514.2 0.0 674.5 1652.8 224.9 0.0 32.1 205.9 0.0 21.5 1060.3 16.0 4402.3 TOTAL SITE ENERGY 4402.27 MBTU 45.5 KBTU/SQFT-YR GROSS-AREA 45.5 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 8369.97 MBTU 86.5 KBTU/SQFT-YR GROSS-AREA 86.5 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.79 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 105 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 139 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. SLincoln Prop 042710 DOE-2.2-47h2 4/21/2011 14:35:51 BDL RUN 1 REPORT- BEPU Building Utility Performance WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- ------- -------- EM1 ELECTRICITY KWH 150647. 0. 197629. 86356. 65908. 0. 9401. 60331. 0. 6298. 0. 4696. 581267. FM1 NATURAL-GAS THERM 0. 0. 0. 13581. 0. 0. 0. 0. 0. 0. 10603. 0. 24184. TOTAL ELECTRICITY 581267. KWH 6.005 KWH /SQFT-YR GROSS-AREA 6.005 KWH /SQFT-YR NET-AREA TOTAL NATURAL-GAS 24184. THERM 0.250 THERM /SQFT-YR GROSS-AREA 0.250 THERM /SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 2.79 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.00 HOURS ANY ZONE ABOVE COOLING THROTTLING RANGE = 105 HOURS ANY ZONE BELOW HEATING THROTTLING RANGE = 139 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. SLincoln Prop 042710 DOE-2.2-47h2 4/21/2011 14:35:51 BDL RUN 1 REPORT- ES-D Energy Cost Summary WEATHER FILE- Project Location --------------------------------------------------------------------------------------------------------------------------------- METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? -------------------------------- ---------------- ----------- ------------------- ---------- ---------- --------- Custom Elec Rate ELECTRICITY EM1 581267. KWH 45659. 0.0786 YES Custom Gas Rate NATURAL-GAS FM1 24184. THERM 17169. 0.7099 YES ========== 62828. ENERGY COST/GROSS BLDG AREA: 0.65 ENERGY COST/NET BLDG AREA: 0.65