LEED v4.1
Existing Retail
Indoor Environmental Quality
Minimum Indoor Air Quality

LEED CREDIT

Retail-EBOM-v4.1 EQp1: Minimum Indoor Air Quality Required

See all forum discussions about this credit »

SPECIAL REPORT

LEEDuser expert

Ben Stanley

WSP - Built Ecology
Senior Sustainability Manager

SPECIAL REPORT

LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To contribute to the comfort and well-being of building occupants by establishing minimum standards for indoor air quality (IAQ).

Requirements

Maintain the ventilation system equipment and associated components based on Table 8.2 of ASHRAE 62.1-2016. Include information on ventilation system operation and preventative maintenance in the current facilities requirements and operations and maintenance plan required for compliance with EA prerequisite Energy Efficiency Best Management Practices.

For spaces with mechanical exhaust, test and confirm proper operation of the exhaust systems as outlined in the current facilities requirements and operations and maintenance plan.

Ventilate the project spaces mechanically or naturally as follows:

For mechanically ventilated spaces, measure the total quantity of outdoor air delivered and verify the results are within 10 percent of the rates outlined in the current facilities requirements and operations and maintenance plan. Measurements shall quantify the amount of outdoor air for each air handling unit serving the project. Measurements taken within five years prior to project submission are acceptable. The rates must meet the following minimum requirements for each air handling unit:

In I-P units:
Minimum outdoor air rate in cfm = 0.06 cfm/sf x gross building area (in sf) + people outdoor air rate from Table 1 (cfm/person) x building occupancy

In SI units:
Minimum outdoor air rate in L/s = 0.3 L/s*m2x gross building area (in m2) + people outdoor air rate from Table 1 (L/s per person) x building occupancy

Table 1. People outdoor air rate

Occupancy category* People outhoor air rate
cfm per person L/s per person
Auditorium seating area
Libraries
Office space
Places of religious worship
5 2.5
Mall common areas
Museums
7.5 3.8
Classrooms
Daycare
General manufacturing
10 5
Health club/aerobics 20 10
*For additional occupancy categories, see Table 6.2.2.1 of ASHRAE 62.1-2016

Alternatively, the rates may meet the Ventilation Rate Procedure outlined in Section 6.2 of ASHRAE 62.1 editions 2016, 2013, 2010, or 2007.

For naturally ventilated spaces, meet the minimum requirements in Table 2:

Table 2. Minimum opening location and size requirements for naturally ventilated spaces*

Opening type Location of opening Size of opening
Maximum distance from operable openings** Minimum opening area***
Single side opening 2 x ceiling height 4% of floor area
Double side opening 5 x ceiling height 4% of floor area
Corner opening 5 x ceiling height (along a line drawn between the two openings that are farthest apart.; for floor area outside line, comply with single side opening)  4% of floor area

*Adopted from Section 6.4.1 of ASHRAE 62.1-2016
**For ceilings that are increasing in height as distance from the openings is increased, the ceiling height shall be determined as the average height of the ceiling within 6 m (20 ft) from the operable openings.
***If the window is covered with louvers, insect screens, or otherwise obstructed, the openable area must be based on the free unobstructed area through the opening.

Multifamily

For all common areas in the building, meet requirements above.

For residential units, have an operable window in each bedroom with the total openable window area a minimum of 4% of the room floor area or meet the following minimum requirements for the entire unit:

In I-P units:
Minimum outdoor air rate in cfm = 0.03 cfm/sf x dwelling unit floor area (in sf) + 7.5 cfm/person x (number of bedrooms + 1)

In SI units:
Minimum outdoor air rate in L/s = 0.15 L/s*m2 x dwelling unit floor area (in m2) + 7.5 cfm/person x (number of bedrooms + 1)

In each full bathroom, have either an exhaust fan that vents directly to the outdoors or an operable window.

Europe ACP: Arbeitsstaettenrichtlinie ASR 5

Projects in Europe may use Arbeitsstaettenrichtlinie ASR 5 or ASR A3.6 as a local equivalent to ASHRAE Standard 62.1-2010, natural ventilation procedure.

India ACP: Mechanically Ventilated

Projects in India may meet the following as a local equivalent to ASHRAE 62.1-2010:

  • For single-zone and 100% outside air systems, National Building Code of India 2005 (NBC 2005) Table 4-air rate requirements in lieu of ASHRAE 62.1-2010 ventilation rate procedure. Only certain space types are eligible.
  • Central Pollution Control Board (CPCB), National Ambient Air Quality Standards in lieu of ASHRAE 62.1-2010, Section 4.
  • NBC 2005 Part 8, section 3, clause 3.2, with additional parameters, in lieu of ASHRAE 62.1-2010, Minimum Requirements, Sections 5-7.
India ACP: Naturally Ventilated NBC

Projects in India may use NBC 2005 Part 8, Section 1, clauses 5.2.1-5.6 and Appendix A: Design for Natural Ventilation from Handbook on Functional Requirements of Buildings (other than Industrial Buildings), also known as SP 41, 1987 as a local equivalent to ASHRAE Standard 62.1-2010, natural ventilation procedure.

India ACP: Naturally Ventilated CPCB

Projects in India may compare outdoor air quality with the CPCB National Ambient Air Quality Standards in lieu of the U.S. national air quality standards as required in ASHRAE Standard 62.1-2010, Section 4.

See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

LEEDuser expert

Ben Stanley

WSP - Built Ecology
Senior Sustainability Manager

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Intent

To contribute to the comfort and well-being of building occupants by establishing minimum standards for indoor air quality (IAQ).

Requirements

Maintain the ventilation system equipment and associated components based on Table 8.2 of ASHRAE 62.1-2016. Include information on ventilation system operation and preventative maintenance in the current facilities requirements and operations and maintenance plan required for compliance with EA prerequisite Energy Efficiency Best Management Practices.

For spaces with mechanical exhaust, test and confirm proper operation of the exhaust systems as outlined in the current facilities requirements and operations and maintenance plan.

Ventilate the project spaces mechanically or naturally as follows:

For mechanically ventilated spaces, measure the total quantity of outdoor air delivered and verify the results are within 10 percent of the rates outlined in the current facilities requirements and operations and maintenance plan. Measurements shall quantify the amount of outdoor air for each air handling unit serving the project. Measurements taken within five years prior to project submission are acceptable. The rates must meet the following minimum requirements for each air handling unit:

In I-P units:
Minimum outdoor air rate in cfm = 0.06 cfm/sf x gross building area (in sf) + people outdoor air rate from Table 1 (cfm/person) x building occupancy

In SI units:
Minimum outdoor air rate in L/s = 0.3 L/s*m2x gross building area (in m2) + people outdoor air rate from Table 1 (L/s per person) x building occupancy

Table 1. People outdoor air rate

Occupancy category* People outhoor air rate
cfm per person L/s per person
Auditorium seating area
Libraries
Office space
Places of religious worship
5 2.5
Mall common areas
Museums
7.5 3.8
Classrooms
Daycare
General manufacturing
10 5
Health club/aerobics 20 10
*For additional occupancy categories, see Table 6.2.2.1 of ASHRAE 62.1-2016

Alternatively, the rates may meet the Ventilation Rate Procedure outlined in Section 6.2 of ASHRAE 62.1 editions 2016, 2013, 2010, or 2007.

For naturally ventilated spaces, meet the minimum requirements in Table 2:

Table 2. Minimum opening location and size requirements for naturally ventilated spaces*

Opening type Location of opening Size of opening
Maximum distance from operable openings** Minimum opening area***
Single side opening 2 x ceiling height 4% of floor area
Double side opening 5 x ceiling height 4% of floor area
Corner opening 5 x ceiling height (along a line drawn between the two openings that are farthest apart.; for floor area outside line, comply with single side opening)  4% of floor area

*Adopted from Section 6.4.1 of ASHRAE 62.1-2016
**For ceilings that are increasing in height as distance from the openings is increased, the ceiling height shall be determined as the average height of the ceiling within 6 m (20 ft) from the operable openings.
***If the window is covered with louvers, insect screens, or otherwise obstructed, the openable area must be based on the free unobstructed area through the opening.

Multifamily

For all common areas in the building, meet requirements above.

For residential units, have an operable window in each bedroom with the total openable window area a minimum of 4% of the room floor area or meet the following minimum requirements for the entire unit:

In I-P units:
Minimum outdoor air rate in cfm = 0.03 cfm/sf x dwelling unit floor area (in sf) + 7.5 cfm/person x (number of bedrooms + 1)

In SI units:
Minimum outdoor air rate in L/s = 0.15 L/s*m2 x dwelling unit floor area (in m2) + 7.5 cfm/person x (number of bedrooms + 1)

In each full bathroom, have either an exhaust fan that vents directly to the outdoors or an operable window.

Europe ACP: Arbeitsstaettenrichtlinie ASR 5

Projects in Europe may use Arbeitsstaettenrichtlinie ASR 5 or ASR A3.6 as a local equivalent to ASHRAE Standard 62.1-2010, natural ventilation procedure.

India ACP: Mechanically Ventilated

Projects in India may meet the following as a local equivalent to ASHRAE 62.1-2010:

  • For single-zone and 100% outside air systems, National Building Code of India 2005 (NBC 2005) Table 4-air rate requirements in lieu of ASHRAE 62.1-2010 ventilation rate procedure. Only certain space types are eligible.
  • Central Pollution Control Board (CPCB), National Ambient Air Quality Standards in lieu of ASHRAE 62.1-2010, Section 4.
  • NBC 2005 Part 8, section 3, clause 3.2, with additional parameters, in lieu of ASHRAE 62.1-2010, Minimum Requirements, Sections 5-7.
India ACP: Naturally Ventilated NBC

Projects in India may use NBC 2005 Part 8, Section 1, clauses 5.2.1-5.6 and Appendix A: Design for Natural Ventilation from Handbook on Functional Requirements of Buildings (other than Industrial Buildings), also known as SP 41, 1987 as a local equivalent to ASHRAE Standard 62.1-2010, natural ventilation procedure.

India ACP: Naturally Ventilated CPCB

Projects in India may compare outdoor air quality with the CPCB National Ambient Air Quality Standards in lieu of the U.S. national air quality standards as required in ASHRAE Standard 62.1-2010, Section 4.

LEEDuser expert

Ben Stanley

WSP - Built Ecology
Senior Sustainability Manager

See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Retail-EBOM-v4.1 EQp1